Measured parameter
Select one of the parameters, such as the parameter
to be measured in the system by the sensor
connected to the actual analog input.
PT
PT PT
PT
TT
TT
TT
Q
Q
DPT
DPT DPT
LT LT
DPT DTT
1
5
2 4
9 10
7
12
8 16 15
3 13 6 14
11
TM062328
Overview of sensor locations
Sensor function, measured
parameter
Pos.
Inlet pressure 1
Diff. press., inlet 2
"Outlet pressure" 3
Diff. press.,outlet 4
Diff. press.,pump 5
Operating mode 6
Press. 2, external 7
Diff. press., ext. 8
Storage tank level 9
Feed tank level 10
Pump flow 11
Flow, external 12
Liquid temp.
TPE3, TPE3 D: The temperature is
measured by the built-in sensor.
13
Temperature 1 14
Temperature 2 15
Diff. temp., ext. 16
Ambient temp. Not shown
Other parameter Not shown
Unit
Available measuring units:
Parameter Possible measuring units
Pressure bar, m, kPa, psi, ft
Level m, ft, in
Flow rate
m
3
/h, l/s, yd
3
/h, gpm
Liquid temp. °C, °F
Other parameter %
Electrical signal
Select signal type:
0.5-3.5 V
0-5 V
0-10 V
0-20 mA
4-20 mA.
Sensor range, minimum value
Set the minimum value of the connected sensor.
Sensor range, maximum value
Set the maximum value of the connected sensor.
Factory setting
See section Factory settings.
Related information
9.5.1 Connection terminals, advanced functional
module, FM 300
17.19 External setpoint function
17.46 Assisted pump setup
17.47 Setup, analog input
35. Factory settings