Activation delay
Pump variant Activation delay
TPE3, TPE3 D -
TPE2, TPE2 D ●
Select the activation delay, T1.
It is the time between the digital signal and the
activation of the selected function.
Range: 0 to 6000 seconds.
Duration timer mode
Select the mode. See figure Duration timer function of
digital inputs.
• Not active
• active with interrupt, mode A
• active without interrupt, mode B
• active with after-run, mode C.
Select the duration time, T2.
It is the time which, together with the mode,
determines how long the selected function is active.
Range: 0 to 15,000 seconds.
T1 T2
T1 T2
T1 T1 T2T2
T1
T1
T2
1
2
3
4
5 6
7 8
TM064949
Duration timer function of digital inputs
Pos. Description
1 Mode C
2 Mode B
3 Mode A
4 Digital input
5 T input > T1 + T2
6 T input < T1 + T2
7 T input
8 T input
Factory setting
See section Factory settings.