8 Troubleshooting
255
8
SMGB0077 rev.0 - 01/2013
8.2 Electronic expansion valve check procedure
Valve position Electronic expansion valve
Locked fully closed
Check the temperature of the piping in the heating process. Failu-
re of the temperature to rise indicates a fault.
Locked slightly open The following conditions indicate a fault:
• Where the freeze protection thermistor temperature is
lower than the intake air temperature.
• Where the unit being inspected stops and other units
continue operating in cooling mode.
Locked fully open