100 6808 Manual  — P/N LS10146-001SK-E:C  09/28/2017
Programming
To edit a zone, follow these steps:
1. Enter the installer code.
2. Press 7 for Program Menu.
3. Press 2 to enter zone menu.
4. Press 1 to edit a zone.
5. Enter the zone number, then press ENTER.
Edit Zone Name
6. Press 1 to edit the selected zone name. You can use words to display a descriptive name for a zone.
Edit Zone Properties
Zone properties consist of, alarm delay characteristics, and heat detector sensitivity.
1. Do steps 1 through 5 of Section 9.3.1.
2. Press 2 to edit the properties of the selected zone.
Figure 9.2  Editing Zone Properties
Alarm Delay Characteristics
The programmed zone type is provided for user reference only. To modify the zone type use the HFSS Honeywell Fire Software Suite.
Table 9.1 list the delay choices and a description of each.
NOTE: See Appendix B for editing names.
Type of Delay Description
1-Count
One Count (No Delay). When this option is enabled, an alarm occurs immediately when a single device 
of any of the following types goes into alarm: detector, manual pull, water flow, Aux1 or Aux2. This is 
considered the most typical operation and is the default for all zones.
2-Count
When this type of alarm delay is used, two or more detectors within the zone must go into alarm in order 
for the zone to report an alarm. Switches of type manual pull, Detector Switches, water flow, Aux1 and 
Aux2 are an exception; they will cause an alarm when only one switch is in alarm. 
When a single detector is in alarm in a 2-Count zone, the system enters a prealarm condition. In a 
prealarm condition, the touchpad PZT beeps and the annunciator display indicates that a prealarm has 
occurred. If the zone has been mapped to an output group for the prealarm event, the output group will 
activate. The prealarm will not be reported to the central station.
Alarm Verification
Alarm verification is an optional false alarm prevention feature that verifies an alarm condition by 
resetting the smoke detector. If the alarm condition still exists by the time the reset cycle has completed, 
the detector will go into alarm. If the detector is no longer in alarm, no report will go to the central station. 
The alarm verification sequence is ignored if the zone is already in alarm.
PAS - Positive Alarm 
Sequence
This option is intended to be used with an acknowledge switch. An alarm is delayed for 15 seconds, 
giving on-site personnel a chance to investigate the alarm. If the acknowledge switch is not activated 
within 15 seconds, an alarm occurs automatically.
If this option is enabled for a zone, the zone will respond to an alarm condition as follows:
The zone will not go into alarm for 15 seconds to allow an on-site operator to activate the 
acknowledge switch.
• If the operator does not press the acknowledge switch within 15 seconds, the zone will go into alarm.
• If the operator presses the acknowledge switch within 15 seconds, a 180-second time-frame will begin 
counting down. This time-frame allows the operator to investigate the cause of the alarm.
• If the operator performs a reset within 180 seconds, the alarm will not occur. 
• If the operator does not perform a reset within 180 seconds, an alarm will occur automatically.
• The P.A.S. feature will be overridden if another alarm occurs.
SNGL ILOCK
See Section 10.6.1 for single interlock releasing operation.
Table 9.1  Alarm Delay Characteristics
Detection type also 
selected from this 
screen (see Table 9.1).