EasyManua.ls Logo

Honeywell 6808 - 5865 Connection to Panel; 5865 Mounting

Honeywell 6808
170 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
46 6808 Manual — P/N LS10146-001SK-E:C 09/28/2017
Control Panel Installation
4.10.1 5865 Connection to Panel
The 5865 connects to the panel via the SBUS. Make connections as shown in Figure 4.35. After the 5865 is connected to the panel, it
must be added to the system. This programming step is described in Section 4.11.
Figure 4.35 5865 Connection to the FACP
4.10.2 5865 Mounting
Mount the 5865-4 to a standard 4-gang electrical box. Mount the 5865-3 to a standard 3-gang electrical box. In Figure 4.36, the 5865-4
attached to a 4-gang box is used as an example.
Figure 4.36 5865 Mounting Example
The 5865 ships with a set of zone description labels that can be inserted into the 5865 board assembly. These labels can be used in a type-
writer or can be written on by hand. Slide the labels under the plexiglass as shown in Figure 4.37. The LEDs will show through the label
when illuminated.
Figure 4.37 Inserting Zone Description Labels
Supervised
Power Limited
Class B

Table of Contents

Related product manuals