6808 Manual — P/N LS10146-001SK-E:C 09/28/2017 137
Reporting
11.2 SIA / Panels PI Modifier Reporting:
Events are sent to the central station as a variable length string:
The event format is:
EEZZZZ
Where:
EE Event code (2 characters)
ZZZZ Event parameter (up to four digits – not zero filled)
1. The account number is sent using an account block that is separate from the event block
2. Multiple events can be sent within a single event block. Events are separated by a “/” character.
3. Event parameter can be either a zone, point or module number.
4. When reporting by point is enabled, the communicator uses a “pi” event to supersedes the actual point event to report the module
the point is linked to.
5. Panel ID is not sent in the SIA event parameters.
For Example see Table 11.4:
Water flow switch trouble pi Exp. ID ST Point # STNNXXPPPP 1 373 Exp. ID Point #
Water flow switch trouble restore pi Exp. ID SJ Point # SJNNXXPPPP 3 373 Exp. ID Point #
Zone-based AUX1 switch alarm pi Exp. ID UA Point # UANNXXPPPP 1 140 Exp. ID Point #
Zone-based AUX1 switch alarm re-
store
pi Exp. ID UH Point # UHNNXXPPPP 3 140 Exp. ID Point #
Zone-based AUX1 switch disabled pi Exp. ID UB Point # UBNNXXPPPP 1 571 Exp. ID Point #
Zone-based AUX1 switch enabled pi Exp. ID UU Point # UUNNXXPPPP 3 571 Exp. ID Point #
Zone-based AUX1 switch trouble pi Exp. ID UT Point # UTNNXXPPPP 1 373 Exp. ID Point #
Zone-based AUX1 switch trouble re-
store
pi Exp. ID UJ Point # UJNNXXPPPP 3 373 Exp. ID Point #
Zone-based AUX2 switch alarm pi Exp. ID UA Point # UANNXXPPPP 1 140 Exp. ID Point #
Zone-based AUX2 switch alarm re-
store
pi Exp. ID UH Point # UHNNXXPPPP 3 140 Exp. ID Point #
Zone-based AUX2 switch disabled pi Exp. ID UB Point # UBNNXXPPPP 1 571 Exp. ID Point #
Zone-based AUX2 switch enabled pi Exp. ID UU Point # UUNNXXPPPP 3 571 Exp. ID Point #
Zone-based AUX2 switch trouble pi Exp. ID UT Point # UTNNXXPPPP 1 373 Exp. ID Point #
Zone-based AUX2 switch trouble re-
store
pi Exp. ID UJ Point # UJNNXXPPPP 3 373 Exp. ID Point #
System-based Wireless Gateway
Trouble
pi Exp. ID UT Point # UTNNXXPPPP 1 373 Exp. ID Point #
System-based Wireless Gateway
Trouble - restore
pi Exp. ID UJ Point # UJNNXXPPPP 3 373 Exp. ID Point #
Wireless Gateway Trouble pi Exp. ID UT Point # UTNNXXPPPP 1 373 Exp. ID Point #
Wireless Gateway Trouble restore pi Exp. ID UJ Point # UJNNXXPPPP 3 373 Exp. ID Point #
SIA Reporting Format Contact ID Reporting Format
SIA pi Modifier SIA
Event Description Module
ID # (If
Any)
SIA
Event
Codes
Parameter Fixed Length
Format NN -
panel ID
XX- SBUS ID
ZZZ- Zone #
PPPP- Point #
GGG- Group #
E- Emergency #
RRRR-Receiver #
Qualifier Event
Code
Group # Contact #
Table 11.3 : Reporting Formats Table
Event
Report
Zone/ Point
Panel ID
Module
Zone ZZZZ
Point
ZZZZ
Fields Sent
SIA Event
Data
Fire Alarm-Zone Zone n/a n/a97 15 n/a EE-ZZ FA15
Fire Alarm-Zone Zone n/a n/a 05 n/a EE-Z FA5
Table 11.4: SIA- Panels - PI Modifier Reporting Examples