6808 Manual — P/N LS10146-001SK-E:C 09/28/2017 115
System Operation
10.2.2 Banner
The banner is the message that displays on the control panel when the system is in normal mode (no alarm or trouble condition exists and
menus are not in use). You can create a customized message that will display instead of the internal (default) message. See Section 9.6.5
for information on customizing the banner.
Figure 10.2 Banner Display Examples
10.3 Menu System
The control panel is easy to operate from the Main Menu. To view the Main Menu press the ENTER or right arrow key on the control
panel or remote annunciator. The Main Menu will appear as shown in Section 10.3.1. Select the desired option. You will be prompted for
as access code if required.
The control panel supports up to 20 access codes. The profile for each access code (or user) can be modified through the network pro-
gramming option (see Section 6.2.5 for access code programming).
10.3.1 Main Menu Overview
The chart below is a brief overview of the Main Menu. These options are described in greater detail throughout this section of the man-
ual.
10.3.2 Using the Menus
10.4 Basic Operation
10.4.1 Setting Time and Date
1. Select 4 for Set Date & Time.
2. Make changes in the fields on the screen. Use right arrow to move through the fields. Use the up or down arrow key to select
options in the fields.
3. When the date and time are correct, press ENTER.
10.4.2 Disable / Enable a Point
1. Select 2 for Point Functions.
2. Select 1 for Disable/Enable Point.
Main Menu Options Description
1 - System Tests
Access to Fire Drill, Indicator Test, Walk Tests, Communicator Test, Clear History
Buffer, Manual AlarmNet Registration and Manual Communicator Reset.
2- Point Functions From here you can enable / disable points.
3 - Event History Display event history on the LCD. See Section 10.4.3 for more information.
4 - Set Time and Date Set time and date for the system.
5- Network Diagnostics Ping Panel and Data Network Status.
6- Network Programming
Access Learn Network, Edit Network Names, Edit Panel ID, Computer Access,
Access Codes, Communicator Options, Sync Network Options.
7- Panel Programming
Brings up a set of menus for programming the panel. These options are described
in detail in Section 9.
8- System Information
Menus to view information about the panel such as model, ID, serial number,
revision, send or receive firmware updates and feature registration activation.
To move through the menus: Use the Up or Down arrow to move through the options in a menu. Use the left
arrow to move to a previous menu.
To select an option: Enter the number of the option, or press ENTER if the option has the = symbol next
to it.
Exit Menu Left arrow