6808 Manual  — P/N LS10146-001SK-E:C  09/28/2017 85
Programming Overview
8.2.2  Output Circuit Mapping
Figure 8.3 is a simple example showing how to assign notification and relay output circuits to groups. For an example of a simple floor 
above/floor below application, see Figure 8.5.
Figure 8.3  Assigning Output Circuits to Groups (Example)
8.2.3   Event Mapping 
There are 11 types of Zone events, 14 types of Panel events, and 6 types of Site events that can be mapped (see Table 8-1). For each 
event type, you can activate the output groups with specific output patterns. Mapping examples are shown in Figure 8.4, Figure 8.5, & 
Figure 8.6.
System Zone Panel Site
Fire
Manual Pull Alarm System Aux 1 Alarm Fire Drill
Water Flow Alarm System Aux 2 Alarm General Fire Alarm
Detector Alarm 
(heat or smoke detectors)
General Fire Supervisory
Zone Aux 1 Alarm  General Fire Pre-Alarm
Zone Aux 2 Alarm
Interlock Alert
Interlock Release
Pre-Alarm
Fire Supervisory
Status Point
CO Alarm
CO Supervisory
Emergency
Table 8-1 Event Types