EasyManua.ls Logo

Honeywell 6808 - LED Wiring; Dry Contact Wiring

Honeywell 6808
170 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
44 6808 Manual — P/N LS10146-001SK-E:C 09/28/2017
Control Panel Installation
4.9.3 LED Wiring
There are four 12-pin connectors on the 5880 board for connecting LEDs. Each LED gets its power from Pin 11. Internal resistors are
sized so that there is approximately 10 mA of current for each LED, no series resistors are required. LED outputs can be mapped to out-
put circuits. See Section 9 for programming details.
Wire the LEDs as shown in Figure 4.32.
On connector P1, Pin 12 is a common open collector output for controlling a PZT. If used, the 5880 PZT will match the PZT pattern of
the on-board annunciator or remote annunciator.
Figure 4.32 5880 Board Layout
4.9.4 Dry Contact Wiring
The 8 input circuits on the 5880 board are for monitoring switch inputs-any type of switch supported by the control panel can be used
with the 5880. For example, you can use a 5880 to monitor pull stations, water flow, tamper, reset, or silence switches.
NOTE: The circuit connected to common “Open Collector Output” (last pin on P1) must be current limited so that no more than 100 mA of
current is allowed to flow into the open collector transistor

Table of Contents

Related product manuals