6808 Manual — P/N LS10146-001SK-E:C 09/28/2017 75
SK, SD and SWIFT™Wireless SLC Device Installation
7.2 List of SD SLC Devices
The following SD SLC devices can be used with the control panel. See the appropriate section number in this manual or the device
installation instructions (packaged with the device) for more information..
7.3 SWIFT Wireless SLC Devices
The WSK-WGI Wireless Gateway acts as a bridge between a group of wireless fire devices and a SLC loop on
the 6808. It is powered by the SLC loop or by a regulated, external 24VDC UL-listed power supply.
Available wireless devices include a photo detector, a photo/heat detector, a fixed-temperature heat detector, a
rate-of-rise detector, and a monitor module. For updated details about wireless devices, system setup and operation see
the SWIFT
®
Smart Wireless Integrated Fire Technology Manual # LS10036-001SK-E for more information.
7.4 Maximum Number of Devices
The 6808 supports SK SD or SWIFT™ SLC devices on one 6808 system. The maximum number of devices per system varies depending
on device protocol. Device support is as follows:
SK Devices–A 6808 system can support a total of 99 SK detectors and 99 SK modules. The SLC points can be all sensors or all
modules or any combination of modules and sensors.
OR
SD Devices–A 6808 system can support a total of 127 SD SLC detectors and modules, in any combination.
OR
SK SWIFT Wireless Devices–A SWIFT Gateway system supports up to 50 devices: 1 SWIFT Gateway and up to 49 (in any
combination) wireless detectors and monitor modules. Multiple Gateways can be used. See the SWIFT manual P/N LS10036-
000SK-E for more information.
7.5 Wiring Requirements for SLC Devices
The following information applies to all SLC devices. Refer to the section that describes the type of device you are installing for details.
Color Guide: -IV = Ivory color, -BL = Black, -WH = White, -WHITE-White
Table 7.1 SK SLC Devices
NOTE: The control panel supports the use of either SD or SK SLC devices. You cannot install both SLC device types on this control panel.
SD
Model Number
Model Name/Description
Install
Sheet PN
SD505-PHOTO Photoelectric smoke detector.
150955
SD505-HEAT Absolute temperature heat detector. Trip point range from 135°F–150°F (0°C–37°C).
SD505-6AB 6" base
SD505-6IB 6" short circuit isolator base I56-3541-00
SD505-6RB 6" relay base I56-3542-00
SD505-6SB 6" sounder base I56-3540-00
SD505-DUCT Duct Smoke Detector. Duct Housing including the SD505- Analog Photoelectric
Smoke Sensor. Intake tubing for duct available in three lengths: SD505-T2 (2.5 foot);
SD505-T5 (5 foot); SD505-T10 (10 foot)
1700-09882
SD505-DUCTR Duct Detector housing with relay base. Duct housing with relay base including
SD505- Analog Photoelectric Smoke detector pre-installed
1700-09882
SD500-PS/-PSDA Single or dual action addressable pull station I56-3632-00
SD500-AIM Addressable input module (switch input), standard size, DIP switch configurable I56-3547-00
SD500-MIM Mini input monitor module (switch input), small size, DIP switch configurable.
SD500-ANM Addressable notification module I56-3544-00
SD500-ARM Addressable relay module DIP switch configurable. I56-3545-00
SD500-SDM Addressable smoke detector module. I56-3546-00
SD500-LIM Line isolator module. Fits in a double gang box. I56-3543-00
SD505-DTS-K Remote test switch & LED indicator for the SD505-DUCTR 1700-09882
Table 7.2 SD SLC Devices