6808 Manual — P/N LS10146-001SK-E:C 09/28/2017 77
SK, SD and SWIFT™Wireless SLC Device Installation
When using T-taps, the total length of all taps and the main bus must be met in addition to the maximum distance requirements for the
various wire gauges
Figure 7.2 Calculating Wire Run Length for T-tap
7.5.2 Wiring SLC in Class A Configuration
Figure 7.3 illustrates how to wire the SLC loop for Class A installations.
Figure 7.3 Class A SLC Configuration
NOTE: Style 6 does not use short circuit isolator devices
NOTE: Style 7 requires an isolator module as the first device on the in and the out loop
NOTE: No t-taps allowed on class A SLC loops