6808 Manual  — P/N LS10146-001SK-E:C  09/28/2017 27
Control Panel Installation
4.2  AC Connection
At installation, connect the AC terminals to the power source as shown in Figure 4.2. It may be necessary for a professional electrician to 
make this connection.
The AC terminals are rated at 120 VAC, 60 Hz, 3.6A.
Figure 4.2  120VAC Power Connection
4.3  Battery Power
The batteries must be sealed lead acid type. Before connecting the batteries to the FACP, make certain that the interconnect cable 
between the batteries is not
 connected. Do not connect the battery jumper cable until the system is completely installed. Observe polarity 
when connecting the batteries
The control panel battery charge capacity is 7.0 to 35 AH. The main control cabinet can house batteries up to 18 AH, larger capacity bat-
teries can be housed in a RBB (see Section 4.3.1 for details). Use 12V batteries of the same AH rating. Determine the correct AH rating 
as per your current load calculation (see Section 3.7).
WARNING: RISK OF ELECTRICAL SHOCK AND EQUIPMENT DAMAGES
Several different sources of power can be connected to this panel. Disconnect all sources of power before servicing. The panel and associated 
equipment may be damaged by removing and/or inserting cards, modules or interconnecting cables while this unit is energized.
WARNING: RISK OF PERSONAL INJURY
Battery contains sulfuric acid which can cause severe burns to the skin and eyes and can destroy fabrics. If contact is made with 
sulfuric acid, immediately flush the skin or eyes with water for 15 minutes and seek immediate medical attention