6808 Manual — P/N LS10146-001SK-E:C 09/28/2017 105
Programming
9.5.2 Point Programming For Internal or External Power Module
To program for an internal or external power module points, follow these steps:
1. Enter the installer code.
2. Select 7 for Program Menu.
3. Press 4 to enter point menu.
4. Press the up or down arrows to select the desired module, then press ENTER. Refer to Section 8.5 for available choices.
5. Enter the number of the circuit or point you wish to edit, then press ENTER. Refer to Table 9.3 for available selections.
6. Select the type by pressing the up or down arrows, then press ENTER.
7. Select the function by pressing the up or down arrows, then press ENTER.
8. Select the group by pressing the up or down arrows, then press ENTER.
9. Edit point name, or press the right arrow to skip point name edit. See Section 9.5.2.
NOTIF
OUTPUT PT Select Group
AUX CONST
Use for auxiliary power applications where the devices require
constant power.
AUX RESET
Use for auxiliary power, resettable applications. See Section
4.13.2 for a description of how this option operates.
AUX DOOR
Use for auxiliary power, door holder applications. For
example, if you were using an auxiliary power supply for door
holders, you would use this option. See Section , "Door Holder
Power" for a description of how this option operates.
RELAY
OUTPUT PT Select Group
Output Point, a general use relay type. Use for applications
requiring a relay, such as fan shutdown, elevator recall, and so
on.
AUX RESET Select Group
Use for auxiliary power, resettable applications. See Section ,
"Resettable Power" for a description of how this option
operates.
AUX DOOR Select Group
Use for auxiliary power, door holder applications. For
example, if you were using an auxiliary power supply for door
holders, you would use this option. See Section , "Door Holder
Power" for a description of how this option operates.
W-GATEWAY
W-SWITCH Same as SWITCH
W-RELAY Same as RELAY
Type Selection Function Latching Option Comments
Table 9.2 SLC Point Programming