138 6808 Manual — P/N LS10146-001SK-E:C 09/28/2017
Reporting
11.3 SIA – Panel Communicator:
(Differences/additional features are underlined)
Events are sent to the Central Station Receiver as a fixed length string:
The event format is:
EEPPMMZZZZ
Where
EE Event code (2 characters)
PP Panel number (2 digits – Zero Filled) (valid range from 1 to 64)
MM Module number (2 digits – Zero Filled) (valid range from 1 to 98, typically
Module information)
ZZZZ Event parameter (4 digits – Zero Filled
) (typically Point, Zone or Circuit
information)
1. The Event field will contain 10 digits including the 2 digit event code (EE), 2 digit panel ID (PP), 2 digit Module Number (MM)
and a 4 digit Event Parameter (ZZZZ).
2. Based on the actual Event Code, the Module Number or Event Parameter fields might not contain pertinent information. In that case
the field will contain zeros.
3. The account number is sent using an account block that is separate from the event block.
4. Multiple events can be sent within a single event block. Events are separated by a “/” character.
5. Event parameter can be a Zone, Point or Circuit Number.
6. “pi” modifier event is not used.
7. Panel can be set to report by either Point or Zone.
Fire Alarm-Point Point n/a 01 n/a 123 EE-ZZ /EE-
ZZZ
pi01/FA123
Fire Alarm-Point Point n/a 33 n/a 203 EE-ZZ /EE-
ZZZ
pi11/FA203
Expander Trouble n/a n/a 11 n/a n/a EE-ZZ ET11
Auto Test n/a n/a n/a n/a n/a EE-Z RP0
Battery Trouble-Panel 32 n/a n/a 98 n/a n/a EE-ZZ YT98
Battery Trouble-Expander
18
n/a n/a 18 n/a n/a EE-ZZ YT18
SLC Loop Shorted n/a n/a 44 n/a n/a EE-ZZ ET44
Program Begin Panel
ID=32
n/a n/a n/a n/a n/a EE-Z LB0
Program Begin Panel ID=
22
n/a n/a n/a n/a n/a EE-Z LB0
AC Power Loss - Panel 22 n/a n/a 98 n/a n/a EE-Z AT0
Fire Trouble Point n/a 97 n/a 200 EE-ZZ /EE-
ZZZ
pi97/FT200
Fire Trouble Zone n/a 97 01 n/a EE-Z FT1
Fire Trouble-Nac Point n/a 98 n/a Nac
Circuit 7
EE-ZZ /EE-
Z
pi98/FT7
Z=Pt. #
Fire Trouble-Nac Zone n/a 98 n/a Nac
Circuit 7
EE-ZZZ FT400
ZZZ=OPG#
Event
Report
Zone/ Point
Panel ID
Module
Zone ZZZZ
Point
ZZZZ
Fields Sent
SIA Event
Data
Table 11.4: SIA- Panels - PI Modifier Reporting Examples