EasyManua.ls Logo

Honeywell 6808 - Table 11.5: SIA REPORTING EXAMPLES

Honeywell 6808
170 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6808 Manual — P/N LS10146-001SK-E:C 09/28/2017 139
Reporting
For examples see Table 11.5.
Event
Report
Zone/
Panel ID
Module
MM
Zone
ZZZZ
Point
ZZZZ
Fields
Sent
SIA Event
Data
Fire Alarm-Zone Zone 32 n/a 15 n/a EE-PP-MM-
ZZZZ
FA32000015
Fire Alarm-Zone Zone 32 n/a 05 n/a EE-PP-MM-ZZZZ FA32000005
Fire Alarm-Point Point 32 01 n/a 123 EE-PP-MM-ZZZZ FA32010123
Fire Alarm-Point Point 21 33 n/a 203 EE-PP-MM-ZZZZ FA21330203
Expander Trouble n/a 15 11 n/a n/a EE-PP-MM-ZZZZ ET15110000
Auto Test n/a 32 n/a n/a n/a EE-PP-MM-ZZZZ RP32000000
Battery Trouble-Panel 32 n/a 32 98 n/a n/a EE-PP-MM-ZZZZ YT32980000
Battery Trouble-Expander 18 n/a 32 18 n/a n/a EE-PP-MM-ZZZZ YT32180000
SLC Loop Shorted n/a 01 44 n/a n/a EE-PP-MM-ZZZZ ET01440000
Program Begin n/a 32 n/a n/a n/a EE-PP-MM-ZZZZ LB32000000
Program Begin n/a 22 n/a n/a n/a EE-PP-MM-ZZZZ LB22000000
AC Power Loss- Panel 22 n/a 22 98 n/a n/a EE-PP-MM-ZZZZ AT22980000
MM = 00
Fire Trouble Point 22 97 n/a 200 EE-PP-MM-ZZZZ FT22970200
Fire Trouble Zone 22 97 1 n/a EE-PP-MM-ZZZZ FT22970001
MM = 00
Fire Trouble-Nac Point 22 98 n/a Nac Circuit 7 EE-PP-MM-ZZZZ FT22980007
ZZZZ=Pt. #
Fire Trouble-Nac Zone 22 98 n/a Nac Circuit 7 EE-PP-MM-ZZZZ FT22980007
ZZZZ=OPG #
Table 11.5: SIA REPORTING EXAMPLES

Table of Contents

Related product manuals