Before You Begin Installing
Current Draw Worksheet for SK SLC Devices
Use Table 3.2 to determine current requirements during alarm/battery standby operation SK SLC devices are installed. The 6808 FACP
supports up to a total of 198 SLC devices, consisting of any combination of Sensors and Modules.
Device
Number of
Devices
Current per Device
Standby
Current
Alarm
Current
For each device use this formula: This column X This column = Current per number of devices.
Fire Panel (Current draw from
battery)
1
Standby: 190mA 190 mA
Alarm: 250mA 250 mA
Addressable SLC Detectors
SK-PHOTO
Standby/Alarm: .30mA
2
mA mA
SK-PHOTO-T mA mA
SK-HEAT mA mA
SK-HEAT-HT mA mA
SK-DUCT (includes PhotoR)
1
SK-ACCLIMATE mA mA
SK-HEAT-ROR mA mA
SK-PHOTO-W SLC
Standby: 200µA mA
Alarm: 4.5mA mA
SK-PHOTO-R-W SLC
Standby: 200µA mA
Alarm: 4.5mA mA
SK-PHOTO-T-W SLC
Standby: 200µA mA
Alarm: 4.5mA mA
SK-HEAT-W SLC
Standby: 200µA mA
Alarm: 4.5mA mA
SK-HEAT-ROR-W SLC
Standby: 200µA mA
Alarm: 4.5mA mA
SK-HEAT-HT-W SLC
Standby: 200µA mA
Alarm: 4.5mA mA
SK-BEAM (without integral test)
SLC Standby/Alarm: 2mA
Aux. Pwr
Standby: 2mA mA
Alarm: 8.5mA mA
SK-BEAM-T (with integral test)
3
SLC Standby/Alarm: 2mA
Aux. Pwr
Standby: 2mA mA
Alarm: 8.5 mA mA
SK-FIRE-CO SLC
Standby: .30 mA mA
Alarm: 7.2 mA mA
Table 3.2 Current Draw Worksheet for SK Devices