6808 Manual — P/N LS10146-001SK-E:C 09/28/2017 21
Before You Begin Installing
Addressable SLC Devices
SK-MONITOR
Standby/Alarm: .375mA
mA mA
SK-MINIMON mA mA
SK-PULL-SA/SK-PULL-DA mA mA
SK-MONITOR-2 Standby/Alarm: .75mA mA mA
SK-MON-10 Standby/Alarm: 3.5mA mA mA
SK-CONTROL
SLC
Standby: .375mA
Alarm: .375mA
mA
mA
Aux.
Power
Standby: 1.7mA mA
Alarm: 7mA mA
SK-CONTROL-6
SLC
Standby: 2.25mA
Alarm: 2.25mA
mA
mA
Aux. Pwr
Standby: 8mA
Alarm: 20mA
mA
mA
SK-RELAY Standby/Alarm: .255mA mA mA
SK-RELAY-6 Standby/Alarm: 1.45mA mA mA
SK-RELAYMON-2
Standby: 1.3mA mA
Alarm: 24mA mA
SK-ZONE
Aux Pwr
Standby: 12mA mA
Alarm: 90mA mA
SLC Standby/Alarm: .27mA mA mA
SK-ZONE-6
Aux Pwr
Standby: 50mA mA
Alarm: 270mA mA
SLC Standby/Alarm: 2mA mA mA
SLC Accessories
B200SR-WH / IV Intelligent
sounder base
Aux Pwr
Standby: .5mA mA
Alarm: 35mA mA
SLC Standby .3mA mA
B200S-WH / IV Intelligent sounder
base
Aux Pwr
Standby: .5mA mA
Alarm: (high vol) 35mA mA
SLC Standby .3mA mA
B200SR-LF-WH / IV Low
Frequency sounder base
Aux Pwr
Standby: 1mA mA
Alarm: 125mA mA
B200S-LF-WH / IV Low Frequency
sounder base
Aux Pwr
Standby .55mA mA
Alarm (high vol) 140mA mA
SLC Standby .30mA mA
B224RB-WH / IV Relay Base Standby/Alarm: .5mA mA mA
RTS151/151 KEY Alarm: 7.5mA
mA
RA100Z Alarm: 10mA
mA
SLC Isolator Devices
SK-ISO (Isolator Module)
(100 max.)
Standby/Alarm: .45mA mA mA
B224BI / IV Isolator Base Standby/Alarm: .5 mA
Accessories Modules
6860 Remote LCD Annunciator
(12 max)
Standby: 25mA mA
Alarm: 50mA mA
5860 Remote LCD Annunciator
Standby 20mA mA
Alarm 25mA mA
6855 Remote LCD Annunciator
Standby: 20mA mA
Alarm: 25mA mA
Device
Number of
Devices
Current per Device
Standby
Current
Alarm
Current
Table 3.2 Current Draw Worksheet for SK Devices