48 6808 Manual — P/N LS10146-001SK-E:C 09/28/2017
Control Panel Installation
A number of programmable options are available for customizing telephone lines. These options are described in Section 9.6.
Figure 4.39 Connection of Telephone Lines
4.13 Notification Appliance/Auxiliary Power Circuits
Four outputs are built-in to the 6808 FACP which can be programmed to be used as NACs (Class A or Class B) or as Aux power.
This section of the manual explains how to install conventional notification appliances and how these terminals can be used for auxiliary
power.
4.13.1 Conventional Notification Appliance
This sub-section of the manual explains how to install conventional notification appliances for Class A and Class B configurations.
Class B Notification Wiring
You must use an appliance from the list of compatible appliances in Appendix A at the back of this manual.
To install a Class B notification appliance circuit:
1. Wire Class B Notification appliances as shown in Figure 4.40.
2. Configure the circuit through programming (see Section 9.5).
Figure 4.40 Class B Notification Appliance Circuit Wiring
Supervised
NOTE: These circuits are considered regulated unless used for releasing type service, in which case they are considered special applications.
EOL 4.7 k
Supervised
Power Limited
Notification Wiring
Alarm Polarity Shown