106 6808 Manual  — P/N LS10146-001SK-E:C  09/28/2017
Programming
10. Repeat Steps 1 through 9 for all circuits.
9.5.3  Point Programming For 5880 and 5865 Modules
To program 5880 or 5865 module points
1. Enter the installer code.
2. Select 7 for Program Menu.
3. Press 4 to enter point menu.
Choices Type Selections
Function Selections for 
each Type
Comments
Enter Point or Circuit 
Select Type
UNUSED
NOTIF OUT NOTIF OUT
CTRL CKT CTRL CKT
AUX_PWR
CONSTANT Constant auxiliary power.
AUX RESET Resettable auxiliary power.
AUX DOOR Door holder auxiliary power.
AUX SYNC
Sounder Sync auxiliary power for System 
Sensor
B SWITCH*
MAN PULL
Refer to comments column of
Table 9.2 for description of these options
Latch or Non-latching feature only appears 
for waterflow, supervisory, tamper, zone 
aux1, zone aux2, system aux1, and 
system aux2
WATERFLOW
SUPERVSY
TAMPER
FIRE DRILL
SILENCE
RESET
PAS_ACK
ZN_AUX1
ZN_AUX2
SYS_AUX1
SYS_AUX2
MAN REL
ILOCK
Select Type
STATUS POINT
Non-latching - Used to activate an ancillary 
Output Group that does not active alarm, 
sound PZT, display status or report events. 
Reset has no affect on this point
A SWITCH* Same as B SWITCH
B DETECT*
2-WIRE SMOKE Used for Class B, 2-wire detectors.
4-WIRE SMOKE Used for Class B, 4-wire detectors.
CO 4-WIRE DET Used for Class B, 4-wire CO detectors.
CO 4-WIRE SUP DET
Latching or Non-latching used for Class B, 
4-wire CO Supervisory detectors
A DETECT*
2-WIRE SMOKE Used for Class A, 2-wire detectors.
4-WIRE SMOKE Used for Class A, 4-wire detectors.
CO 4-WIRE DET Used for Class A, 4-wire CO detectors.
CO 4-WIRE SUP DET
Latching or Non-latching used for Class A, 
4-wire CO Supervisory detectors
Select Group
Group or Zone selection will appear 
depending on the type selected.
Edit Name See Section 
9.5.2.
* Only applicable for 5895XL
Table 9.3   Menu Choices for Internal/External Power Module