24 6808 Manual — P/N LS10146-001SK-E:C 09/28/2017
Before You Begin Installing
The FACP can only support 5 devices w/LED’s on. This current draw has been added to the panels alarm current.
If using 24 VDC aux power only. No standby or alarm current for battery calculation if using 24 VAC, 120 VAC or 240 VAC.
If using door holders, you do not need to consider door holder current for alarm/battery standby, because power is removed during that
time. However, during normal operation, door holders draw current and must be included in the 6.0A total current that can be drawn from
the panel.
Use next size battery with capacity greater than required.
5865-4 LED Annunciator
(with reset and silence switches)
(8 max.) Standby: 35 mA mA
Alarm: 145 mA mA
5865-3 LED Annunciator Standby: 35 mA mA
Alarm: 145 mA mA
5880 LED I/O Module Standby: 35 mA mA
Alarm: 200 mA mA
5883 Relay Interface (32 max.) Standby: 0 mA mA
Alarm: 220 mA
(22 mA per relay)
mA
5496 NAC Expander (8 max.) Standby/Alarm: 10 mA mA mA
5895XL Power Supply Standby/Alarm: 10 mA mA mA
Network Cards
SK-NIC Network Interface Card (1 Max.) Standby/Alarm: 21 mA mA mA
SK-FML Fiber Optic Multi Mode (1 Max.) Standby/Alarm: 53 mA mA mA
SK-FSL Fiber Optic Single Mode (1 Max.) Standby/Alarm: 79 mA mA mA
A Total System Current
Auxiliary Devices
3
Refer to devices manual for current rating.
IPDACT-2 IP Communicator Alarm: 136 mA
mA
Standby: 93 mA mA
IPDACT-2UD IP Communicator Alarm: 155 mA mA
Standby: 98 mA mA
CELL-MOD/CELL-CAB-SK Standby: 55 mA mA
Alarm: 100 mA mA
Alarm/Standby: mA mA mA
Alarm/Standby: mA mA mA
Alarm/Standby: mA mA mA
B Auxiliary Devices Current
Notification Appliance Circuits Refer to devices manual for current rating.
5495/5499 Power Supply 24 VDC One input circuit: 15 mA
mA
Both input circuits: 30 mA
mA
Alarm: mA
mA
Alarm: mA
mA
Alarm: mA
mA
Alarm: mA
mA
C Notification Appliances Current
mA
D Total current ratings of all devices in system (line A + line B + C) mA mA
E Total current ratings converted to amperes (line D x .001): A A
F Number of standby hours (24 or 60 for NFPA 72, chapter 1, 1-5.2.5): H
G Multiply lines E and F. Total standby AH AH
H Alarm sounding period in hours. (For example, 5 minutes =.0833 hours) H
I Multiply lines E and H. Total alarm AH
AH
J Add lines G and I.
4
AH
Multiply by the Derating Factor x 1.25
Total ampere hours
required
Device
Number of
Devices
Current per Device
Standby
Current
Alarm
Current
Table 3.3 Current Draw worksheet for SD Devices