LS10143-001SK-E Reporting
12-6
Supervisory Detector Alarm
Restore
FR Zone # FRNN000ZZZ 3 200 00 Zone #
Supervisory/Tamper Alarm FS Zone # FSNN000ZZZ 1 200 00 Zone #
Supervisory/Tamper alarm condi-
tion restore
FR Zone # FRNN000ZZZ 3 200 00 Zone #
Supervisory/Tamper switch
trouble
FT Zone # FTNN000ZZZ 1 373 00 Zone #
Supervisory/Tamper switch
trouble restore
FJ Zone # FJNN000ZZZ 3 373 00 Zone #
System-based AUX1 switch
alarm
UA 1000 UANN001000 1 140 01 000
System-based AUX1 switch
alarm restore
UH 1000 UHNN001000 3 140 01 000
System-based AUX1 switch trou-
ble
UT 1000 UTNN001000 1 373 01 000
System-based AUX1 switch trou-
ble restore
UJ 1000 UJNN001000 3 373 01 000
System-based AUX2 switch
alarm
UA 2000 UANN002000 1 140 02 000
System-based AUX2 switch
alarm restore
UH 2000 UHNN002000 3 140 02 000
System-based AUX2 switch trou-
ble
UT 2000 UTNN002000 1 373 02 000
System-based AUX2 switch trou-
ble restore
UJ 2000 UJNN002000 3 373 02 000
Voice Aux ECS 1 Alarm UA 3 UANN003000 1 171 00 000
Voice Aux ECS 1 Alarm Restore UH 3 UHNN003000 3 171 00 000
Voice Aux ECS 2 Alarm UA 4 UANN004000 1 172 00 000
Voice Aux ECS 2 Alarm Restore UH 4 UHNN004000 3 172 00 000
Voice Aux ECS 3 Alarm UA 5 UANN005000 1 173 00 000
Voice Aux ECS 3 Alarm Restore UH 5 UHNN005000 3 173 00 000
Voice Aux ECS 4 Alarm UA 6 UANN006000 1 174 00 000
Voice Aux ECS 4 Alarm Restore UH 6 UHNN006000 3 174 00 000
Water flow switch alarm SA Zone # SANN000ZZZ 1 113 00 Zone #
Water flow switch alarm Restore SH Zone # SHNN000ZZZ 3 113 00 Zone #
Water flow switch trouble ST Zone # STNN000ZZZ 1 373 00 Zone #
Water flow switch trouble Restore SJ Zone # SJNN000ZZZ 3 373 00 Zone #
Table 12-2: Reporting Formats Table
SIA Reporting Format
Contact ID Reporting Format
SIA pi Modifier SIA IFP-2100/ECS
Event Description Module
ID # (If
Any)
SIA
Event
Codes
Parameter Fixed Length
Format NN -
panel ID
XX- SBUS ID
ZZZ- Zone #
PPPP- Point #
GGG- Group #
E- Emergency #
RRRR-Receiver #
Qualifier Event
Code
Group # Contact #

Table of Contents

Other manuals for Honeywell ECS Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell ECS Series and is the answer not in the manual?

Honeywell ECS Series Specifications

General IconGeneral
BrandHoneywell
ModelECS Series
CategoryConference System
LanguageEnglish

Related product manuals