LS10143-001SK-E Reporting
12-10
Manual pull switch trouble pi Exp. ID FT Point # FTNNXXPPPP 1 373 Exp. ID Point #
Manual pull switch trouble restore pi Exp. ID FJ Point # FJNNXXPPPP 3 373 Exp. ID Point #
Manual release switch alarm
(Water Release Zone)
pi Exp. ID FA Point # FANNXXPPPP 1 110 Exp. ID Point #
Manual release switch alarm re-
store (Water Release Zone)
pi Exp. ID FH Point # FHNNXXPPPP 3 110 Exp. ID Point #
Manual release switch disabled pi Exp. ID FB Point # FBNNXXPPPP 1 571 Exp. ID Point #
Manual release switch enabled pi Exp. ID FU Point # FUNNXXPPPP 3 571 Exp. ID Point #
Manual release switch trouble
(Water Release Zone)
pi Exp. ID FT Point # FTNNXXPPPP 1 373 Exp. ID Point #
Manual release switch trouble re-
store (Water Release Zone)
pi Exp. ID FJ Point # FJNNXXPPPP 3 373 Exp. ID Point #
Notification output point disabled pi Exp. ID FB Point # FBNNXXPPPP 1 571 Exp. ID Point #
Notification output point enabled pi Exp. ID FU Point # FUNNXXPPPP 3 571 Exp. ID Point #
Notification output point trouble pi Exp. ID FT Point # FTNNXXPPPP 1 320 Exp. ID Point #
Notification output point trouble
restore
pi Exp. ID FJ Point # FJNNXXPPPP 3 320 Exp. ID Point #
Positive Alarm Sequence ac-
knowledge switch disabled
pi Exp. ID FB Point # FBNNXXPPPP 1 571 Exp. ID Point #
Positive Alarm Sequence ac-
knowledge switch enabled
pi Exp. ID FU Point # FUNNXXPPPP 3 571 Exp. ID Point #
Positive Alarm Sequence ac-
knowledge switch trouble
pi Exp. ID FT Point # FTNNXXPPPP 1 373 Exp. ID Point #
Positive Alarm Sequence ac-
knowledge switch trouble restore
pi Exp. ID FJ Point # FJNNXXPPPP 3 373 Exp. ID Point #
Status Point Trouble pi Exp. ID UT Point # UTNNXXPPPP 1 379 Exp. ID Point #
Status Point Trouble Restored pi Exp. ID UJ Point # UJNNXXPPPP 3 379 Exp. ID Point #
Status Point is Disabled pi Exp. ID UB Point # UBNNXXPPPP 1 580 Exp. ID Point #
Status Point is Enabled pi Exp. ID UU Point # UUNNXXPPPP 3 580 Exp. ID Point #
Supervisory/Tamper Alarm pi Exp. ID FS Point # FSNNXXPPPP 1 200 Exp. ID Point #
Supervisory/Tamper Alarm
Restore
pi Exp. ID FR Point # FRNNXXPPPP 3 200 Exp. ID Point #
Supervisory/Tamper point dis-
abled
pi Exp. ID FB Point # FBNNXXPPPP 1 571 Exp. ID Point #
Supervisory/Tamper point en-
abled
pi Exp. ID FU Point # FUNNXXPPPP 3 571 Exp. ID Point #
Supervisory/Tamper point trouble pi Exp. ID FT Point # FTNNXXPPPP 1 373 Exp. ID Point #
Table 12-2: Reporting Formats Table
SIA Reporting Format
Contact ID Reporting Format
SIA pi Modifier SIA IFP-2100/ECS
Event Description Module
ID # (If
Any)
SIA
Event
Codes
Parameter Fixed Length
Format NN -
panel ID
XX- SBUS ID
ZZZ- Zone #
PPPP- Point #
GGG- Group #
E- Emergency #
RRRR-Receiver #
Qualifier Event
Code
Group # Contact #

Table of Contents

Other manuals for Honeywell ECS Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell ECS Series and is the answer not in the manual?

Honeywell ECS Series Specifications

General IconGeneral
BrandHoneywell
ModelECS Series
CategoryConference System
LanguageEnglish

Related product manuals