Model IFP-2100/ECS Installation Manual LS10143-001SK-E
12-9
ECS Control Circuit Trouble pi Exp. ID QT Point # QTNNXXPPPP 1 320 Exp. ID Point #
ECS Control Circuit Trouble Re-
stored
pi Exp. ID QJ Point # QJNNXXPPPP 3 320 Exp. ID Point #
ECS Relay Trouble pi Exp. ID QT Point # QTNNXXPPPP 1 320 Exp. ID Point #
ECS Relay Trouble Restored pi Exp. ID QJ Point # QJNNXXPPPP 3 320 Exp. ID Point #
ECS Notification Trouble pi Exp. ID QT Point # QTNNXXPPPP 1 320 Exp. ID Point #
ECS Notification Trouble Re-
stored
pi Exp. ID QJ Point # QJNNXXPPPP 3 320 Exp. ID Point #
External Reset/Silence/Fire Drill
switch disabled
pi Exp. ID UB Point # UBNNXXPPPP 1 571 Exp. ID Point #
External Reset/Silence/Fire Drill
switch enabled
pi Exp. ID UU Point # UUNNXXPPPP 3 571 Exp. ID Point #
External Reset/Silence/Fire Drill
switch trouble
pi Exp. ID UT Point # UTNNXXPPPP 1 373 Exp. ID Point #
External Reset/Silence/Fire Drill
switch trouble restore
pi Exp. ID UJ Point # UJNNXXPPPP 3 373 Exp. ID Point #
Interlock switch alarm (Water Re-
lease Zone)
pi Exp. ID FA Point # FANNXXPPPP 1 110 Exp. ID Point #
Interlock switch alarm restore
(Water Release Zone)
pi Exp. ID FH Point # FHNNXXPPPP 3 110 Exp. ID Point #
Interlock switch disabled pi Exp. ID FB Point # FBNNXXPPPP 1 571 Exp. ID Point #
Interlock switch enabled pi Exp. ID FU Point # FUNNXXPPPP 3 571 Exp. ID Point #
Interlock switch trouble (Water
Release Zone)
pi Exp. ID FT Point # FTNNXXPPPP 1 373 Exp. ID Point #
Interlock switch trouble restore
(Water Release Zone)
pi Exp. ID FJ Point # FJNNXXPPPP 3 373 Exp. ID Point #
LOC Mic Activated ECS Alarm pi Exp. ID QA 0 QANNXX0000 1 220 Exp. ID 000
LOC Mic Activated ECS Alarm
Restore
pi Exp. ID QH 0 QHNNXX0000 3 220 Exp. ID 000
LOC ECS # Alarm pi Exp. ID QA Emergen-
cy #
QANNXXE000 1 220 +
Emer-
gency #
Exp. ID 000
LOC ECS # Alarm Restore pi Exp. ID QH Emergen-
cy #
QHNNXXE000 3 220 +
Emer-
gency #
Exp. ID 000
Manual pull switch alarm pi Exp. ID FA Point # FANNXXPPPP 1 115 Exp. ID Point #
Manual pull switch alarm restore pi Exp. ID FH Point # FHNNXXPPPP 3 115 Exp. ID Point #
Manual pull switch disabled pi Exp. ID FB Point # FBNNXXPPPP 1 571 Exp. ID Point #
Manual pull switch enabled pi Exp. ID FU Point # FUNNXXPPPP 3 571 Exp. ID Point #
Table 12-2: Reporting Formats Table
SIA Reporting Format
Contact ID Reporting Format
SIA pi Modifier SIA IFP-2100/ECS
Event Description Module
ID # (If
Any)
SIA
Event
Codes
Parameter Fixed Length
Format NN -
panel ID
XX- SBUS ID
ZZZ- Zone #
PPPP- Point #
GGG- Group #
E- Emergency #
RRRR-Receiver #
Qualifier Event
Code
Group # Contact #