80 NCA-2 Manual — P/N 52482:M5 03/20/2019
Programming Point Program Menu
5.5.8 MORE Menu
Pressing “MORE” at the Panel Program Menu will bring up the Event Logging screen.
Figure 5.37 Panel Program Menu: More
Press the appropriate soft key to toggle between YES (log the event activation) and NO (do not log the event activation.
5.6 Point Program Menu
The point program menu allows the programmer to change the volume setting on any networked DVC or DAA or program Logic Equa-
tions.
Figure 5.38 Point Programming Menu
EVENT LOGGING
NON-FIRE ACTIVATION: NO
OUTPUT ACTIVATION: NO
ACCEPT
BACK
Main menu
Program/alter status menu
Panel Program menu
More
POINT PROGRAM MENU
POINT SELECT
N078AA00
(AMPLIFIER)
NEXT POINT ACCEPT
PREVIOUS POINT BACK
Type Address Format
LOGIC ZONE ZLyyyy ZL=Logic Zone, yyyy=Logic Zone number(1-1000)
DVC/DAA NxxxAAyy N = Node, xxx=DVC or DVC-EM Node number, AA = DAA Audio Amplifier, yy=DAA address
(01 through 32).
Note: When yy=00, the address format is the DVC or DVC-EM address.
ACS Ayy+Custom Label A=Annunciator, yy=Annunciator address
GENERAL
ZONE
Zyyy Z=General Zone, yyy=General Zone number
Table 5.5 Address Formats

Table of Contents

Other manuals for Honeywell Notifier AFP-100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Notifier AFP-100 and is the answer not in the manual?

Honeywell Notifier AFP-100 Specifications

General IconGeneral
BrandHoneywell
ModelNotifier AFP-100
CategoryControl Panel
LanguageEnglish

Related product manuals