NCA-2 Manual — P/N 52482:M5 03/20/2019 9
Programming Features Subject to AHJ Approval About this Manual
Regional Settings Yes Yes Singapore
Chicago
Australia
China
Canada
Chicago Canada
DCC Enable Yes Yes Yes
No
Yes or No Yes
Trouble Reminder Yes Yes 4 Hours
24 Hours
4 Hours 4 Hours
Alarm Reminder Yes Yes Off
24 Hours
24 Hours 24 Hours
Supervisory Reminder Yes Yes Off
24 Hours
24 Hours 24 Hours
CO Reminder Yes Yes Off
24 Hours
24 Hours 24 Hours
This product incorporates field-programmable software. In order for the product to comply with the requirements in the
Standard for Control Units and Accessories for Fire Alarm Systems, UL 864/ULC-S527, certain programming features or
options must be limited to specific values or not used at all as indicated below.
Program Feature or Option
Permitted in UL
864? (Y/N)
Permitted in
ULC-S527? (Y/N)
Possible
Settings
Settings
Permitted in UL
864
Settings
Permitted in
ULC-S527