NCA-2 Manual — P/N 52482:M5 03/20/2019 57
Alter Status Menu Programming
5.3 Alter Status Menu
5.3.1 Alter Status Menu Options
After you enter the correct password/user ID and press the ALTER STATUS soft key from the Program/Alter Status menu, the NCA-2
navigates to the screen with menu options shown in Figure 5.5. BACK or <ESC> will return to the PROGRAM/ALTER STATUS
ENTRY screen discussed in “After a valid password is entered, the NCA-2 will navigate to the PROGRAM/ALTER STATUS ENTRY
screen. There are three possible menus, which are detailed in the upcoming sections:” on page 56.
Figure 5.5 Alter Status Menu
5.3.2 Disable/Enable
Disable/enable individual control points on a remote fire panel node. It is for use across a network only; not for use with display nodes
such as the NCA-2 or NCS.
Figure 5.6 is displayed when you select DISABLE/ENABLE from the Alter Status Menu. Identify which point(s) to disable/enable. If
there is an event in the display area, that address will be the default. This allows you to quickly read the point being displayed. If no
event is present, the default format is that of a detector. To scroll through device types, press the POINT SELECT soft key. When you
have selected the desired device type, enter the device address, then press the ACCEPT soft key to accept the entry or <ESC> to exit.
The soft key BACK will also exit without saving. The NCA-2 will display the Enable/Disable screen. If the point does not exist or the
node is off-line, the NCA-2 will display an error screen. This screen will be displayed for three seconds and return to the previous screen.
After selecting a point, the NCA-2 will display that point and give the option of enabling or disabling it. If the point is enabled, the cor-
responding option is not visible, letting the user know the current setting of that point. To exit the screen without changing the
enable/disable status, press BACK or the <ESC> key.
Figure 5.6 Alter Status: Disable/Enable Point, Point Select
TROUBLE
PROG MODE ACTIVATED
NODE LABEL FOR LOCAL NCA-2
10:48:52A TUE JAN 22, 2019 N009
ALTER STATUS MENU
DISABLE/ENABLE WALK TEST
DETECTOR SENSITIVITY CHANGE TIME/DATE
CLEAR VERIFY COUNTS N000 CONTROL ON/OFF
CLEAR HISTORY BACK
Main menu
Program/alter status
Alter status
TROUBLE
PROG MODE ACTIVATED
NODE LABEL FOR LOCAL NCA-2
10:48:52A TUE JAN 22, 2019 N009
POINT SELECT
POINT SELECT:
NxxxLyyDzzz (DETECTOR)
NEXT POINT ACCEPT
PREVIOUS POINT BACK
Main menu
Program/alter status
Alter status
Disable/enable point
Types of points
available vary
depending on
FACP. (see
“Read Status” on
page 45 for
panel limitations.

Table of Contents

Other manuals for Honeywell Notifier AFP-100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Notifier AFP-100 and is the answer not in the manual?

Honeywell Notifier AFP-100 Specifications

General IconGeneral
BrandHoneywell
ModelNotifier AFP-100
CategoryControl Panel
LanguageEnglish

Related product manuals