43 ST 800 Pressure Transmitter User’s Manual Revision 15
Set LRV
[ 8SETLRV]
Set LRV
Executing this selection performing
for Zero operation. Note: The PV
value shown in bottom line will be
available in Pressure Units (Simple
Display pressure unit)
Press to
enter menu
selection
Press to
initiate action
Set URV
[ 9SETURV]
Set URV
Executing this selection for Span
operation
Note: The PV value shown in
bottom line will be available in
Pressure Units (Simple Display
pressure unit)
Contrast
[10CNTRST]
Contrast level
Adjust the LCD contrast level.
Range from » (1) to
»»»»»»»»» (7)
Default: »»»»»»» (7)
Press to
enter Menu
selection
Menu to
select level.
to Enter
LRV Corrects
[11LRVCOR]
Calibration Methods
Perform an input calibration
correction by applying process input
at the configured LRV level.
Press to
enter menu
selection
Press to
initiate action
URV Corrects
[12URVCOR]
Calibration Methods
Perform an input calibration
correction by applying process input
at the configured URV level.
Press to
enter menu
selection
Press to
initiate action
Reset Corrects
[13RSTCOR]
Calibration Methods
Executing this selection resets the
Zero, LRV, URV, Cal Low, Cal
High and Barometric Standard
Corrects back to factory values.
Press to
enter menu
selection
Press to
initiate action