26 ST 800 Pressure Transmitter User’s Manual Revision 15
Table 10 – Diagnostics Menu
All Diagnostics menu items are Read Only.
<Return> Return to the Level 1 menu
FAULT: There is a problem with the meter
body
FAULT: There is a problem with the
electronics module (HART, DE, or FF)
FAULT: There is a problem with the
interface between the meter body and the
electronics module.
Shows the number of Non-Critical
Diagnostics that are currently active
Normal indicates that the Loop Output
reflects the current value of the PV.
FIXED OUTPUT indicates that the Loop
Output of the transmitter is manually set a
fixed value, probably due to a DAC
Trim or Loop Test operation that is
currently in progress.
EXCESSIVE: Input applied exceeds 5%
of expected value (as defined by LRV).
EXCESSIVE: Input applied exceeds
5% of expected value (as defined by URV).
LOW: Supply voltage is below the low
specification limit.
HIGH: Supply voltage is above the high
specification limit.
OVERLOAD: Input pressure is greater
than 200% URL (DP) or 150% URL (GP,
AP).
OVERTEMP: Meter body temperature
is greater than 125 C.
OVERTEMP: Electronics temperature
is greater than 85 C.
SUSPECT: The interface between the
meter body and the electronics module is
experiencing intermittent
communication failures.
The transmitter has not been calibrated by
the factory.
The DAC has not been compensated for
temperature effects. This is a factory
operation.