77 ST 800 Pressure Transmitter User’s Manual Revision 15
Custom Tag

Enter Custom Tag using and
alphanumeric value up to 14
characters long
Press to enter
menu selection
and to select
Alphanumeric
to enter and
shift to next char.
Range / Cal Units
atm, bar ftH2O
@ 68ºF gf/cm2
inH2O @ 39ºF
inH2O @ 60ºF
inH2O @ 68ºF inHg
@ 0ºC kgf/cm2,
kPa mbar,
mmH2O @ 4ºC,
mmH2O @ 68ºF,
mmHg @ 0ºC,
MPa, Pa,
psi
Torr,
mH2O @ 4ºC mHg
@ 0ºC
Choose engineering units for LRV,
URV and Corrects values
Press to enter
menu selection
and to select
from list
to enter
Pressure Units
(Available only when
Pressure PV display
is selected)
atm, bar ftH2O
@ 68ºF gf/cm2
inH2O @ 39ºF
inH2O @ 60ºF
inH2O @ 68ºF inHg
@ 0ºC kgf/cm2,
kPa mbar,
mmH2O @ 4ºC,
mmH2O @ 68ºF,
mmHg @ 0ºC,
MPa, Pa,
psi
Torr,
mH2O @ 4ºC mHg
@ 0ºC
Choose appropriate engineering units
from list
Press to enter
menu selection
and to select
from list
to enter
Zero Correct
Do Correct
Executing this selection corrects
the Zero based on the input pressure
Press to enter
menu selection
Press to
initiate action
LRV Correct
Do Correct
Executing this selection corrects the
LRV based on the input pressure
URV Correct
Do Correct
Executing this selection corrects the
LRV based on the input
pressure
Reset Corrects
Do Correct
Executing this selection Resets the
Zero, LRV, and URV Corrects back
to Factory values