HP BladeSystem Insight Display troubleshooting  19 
Symptoms: HP BladeSystem c7000 Enclosure Insight Display 
 
  Symptoms  Initial step  Required steps 
The display screen is off, and the buttons 
do not operate. 
Press any Insight Display button to try to 
wake up the display. The Insight Display 
powers on automatically if the health is 
good. 
Begin with step 1. 
The display screen flashes, and the Insight 
Display buttons do not operate. 
Press any Insight Display button to stop the 
flashing. The Insight Display flashes when 
any of the following are true: 
  After inactivity if the health is degraded 
or failed  
  The UID is on 
  A chat message has been sent to the 
enclosure 
Begin with step 1. 
 
 
Procedures: HP BladeSystem c7000 Enclosure Insight Display 
 
 
CAUTION:   Some troubleshooting procedures require powering down an entire enclosure. To 
avoid possible data loss, always secure permission before powering down an enclosure. 
 
 
 
CAUTION:   If you are using a Virtual Connect environment, some of these procedures might 
cause the loss of Virtual Connect credentials and the loss of communication between the Onboard 
Administrator and the Virtual Connect Interconnect module. Ensure the Virtual Connect 
configuration is backed up before proceeding with any of the following procedures. Virtual 
Connect configuration can be backed up by using Virtual Connect GUI or Virtual Connect 
Support Utility. 
 
 
  
CAUTION:   To avoid data loss, do not remove an Onboard Administrator when the Insight 
Display shows a firmware update in progress. During this activity, the Insight Display displays the 
Firmware Update screen with the Lock icon and the firmware update progress bar. 
 
For the steps in this table, use the following definitions for all variables: 
•  Standby Onboard Administrator = Suspect OA #Y 
•  Y = Original bay location for the standby module 
•  Second module = Suspect OA #X 
•  X = Original bay location of the active module 
 
Step  HP BladeSystem c7000 Enclosure Insight Display action and verification 
Step 1 
Action 
Check the Onboard Administrator health LED. 
 
Verification 
If the Onboard Administrator health LED is on, then continue to the next step. 
If the Onboard Administrator health LED is off, then perform the following substeps: 
1  Check the power to the enclosure.  
2  Be sure that the power supplies are installed and are operating properly.   
3  Complete step 1 again.