Chapter 5
Site Preparation
Power Options
160
To verify the proper wiring to a 5-wire PDCA, use a DVM to measure the voltage at the test points.
Voltage should read 200-240VAC phase-to-neutral, as measured between the test points as follows:
L1 to N, L2 to N, L3 to N.
Figure 5-13 Cable Preparation Detail
NOTE Dimensions shown are for a cable strain relief without an extension nipple. If an extension
nipple is used, then the cable jacket must removed accordingly.