Chapter 5
Site Preparation
Power Options
162
Customer Installation Options
Figure 5-16 and Figure 5-17 detail a suggested configuration for connecting the PDCA when the use of rigid
conduit is required or desired. Using a 2- to 4-inch nipple and a 90o elbow allows the conduit to pass through
the raised floor at a point immediately past the cabinet. This prevents the conduit from extending beyond the
cabinet.
Figure 5-16 PDCA Conduit Connection