Appendix A Parameters Shenzhen Hpmont Technology Co., Ltd.
- 124 - HD3N Series User Manual V1.1
Function
Setting Range Default
Unit
Attribute Setting
F09.04 V/f voltage of motor (V2) F09.06 - F09.02 0.0% 0.1%
×
F09.05
V/f frequency of motor
(F1)
0.0% - F09.03 0.0% 0.1%
×
F09.06 V/f voltage of motor (V1) 0.0% - F09.04 0.0% 0.1%
×
F09.07 Torque boost of motor
0.0 - 30.0%
0.0%: Auto torque boost
2.0% 0.1%
×
F09.08
Cut-off point used for
manual torque boost of
motor
0.0 - 50.0% (F08.03) 25.0% 0.1%
○
F09.09
Slip compensation gain of
motor
0.0 - 300.0% 0.0% 0.1%
○
F09.10
Slip compensation filter
time of motor
0.01 - 10.00s 0.10s 0.01s
○
F09.11
Slip compensation limit of
motor
0.0 - 250.0% 200.0% 0.1%
×
F09.12 Motor iron loss 0.000 - 9.999kW
Depend
on HD3N
0.001kW
×
F09.14
AVR (automatic voltage
regulation) function of
motor
0: Disabled
1: Enabled all the time
2: Disabled in Dec process
1 1
○
F09.15
Low frequency oscillation-
suppression of motor
0 - 200 50 1
○
F09.16
High frequency
oscillation-suppression of
motor
0 - 200 20
1
○
F09.17
Energy saving control
selection
0: Invalid
3: Enabled according to output
current
0 1
×
F09.18
Motor energy saving
coefficient
0.0 - 100.0% 5.0% 0.1%
○
F09.19
Starting frequency of
motor energy saving
0.00 - 50.00Hz 25.00Hz 0.01Hz
○
F09.20
Switching point of motor
energy saving
0.0 - 100.0% 100.0% 0.1%
○
F09.21
Detection times of motor
energy saving
0 – 5000times 10times 1times
○
F09.22
Voltage recovery time of
motor energy saving
40 - 4000ms 100ms 1ms
○
F09.23
Voltage decrease time of
motor energy saving
40 - 4000ms 100ms 1ms
○
F10: Motor Vector Control Speed-loop Parameters ( on pages 71 - 72)
F10.00
Proportional gain 1 of
motor speed control
0.1 - 200.0 10.0 0.1
○
F10.01
Integral time 1 of motor
speed control
0.00 - 10.00s 0.10s 0.01s
○