Materials: electric heating belt, tinfoil, thermal insulation foam
Skill requirement: common technician
Procedure
Step 1 Wrap the electric heating belt around the drainpipe and water rell pipe outside
the pre-fab. module.
● The drainpipe is pre-integrated with the electric heating belt in the outdoor unit
compartment. The outdoor part is reserved in the outdoor unit compartment and needs
to be routed onsite.
● The water rell pipe needs to be routed onsite.
Figure 8-7 Wrap the electric heating belt around the drainpipe and water
rell
pipe
Step 2 Wrap the electric heating belt and pipes with tinfoil.
Step 3 Secure the temperature probe to the pipe using a cable tie.
Secure the temperature probe to the position on the water rell and drainage pipe. The
position is the point where the electric heating belt is wrapped 50 cm long around the
water
rell and drainage pipe from the water rell and drainage pipe port.
FusionDC1000A Prefabricated All-in-One Data
Center
Installation Guide (IT Scenario) 8 Installing Devices Inside the Pre-fab. Module
Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd. 73