Materials: electric heating belt, tinfoil, thermal insulation foam
Skill requirement: common technician
Procedure
Step 1 Wrap the electric heating belt around the drainpipe and water rell pipe outside
the pre-fab. module.
NO TE
The drainpipe is pre-integrated with the electric heating belt in the outdoor unit
compartment. The outdoor part is reserved in the outdoor unit compartment and needs
to be routed onsite.
The water rell pipe needs to be routed onsite.
Figure 8-7 Wrap the electric heating belt around the drainpipe and water
rell
pipe
Step 2 Wrap the electric heating belt and pipes with tinfoil.
Step 3 Secure the temperature probe to the pipe using a cable tie.
NO TE
Secure the temperature probe to the position on the water rell and drainage pipe. The
position is the point where the electric heating belt is wrapped 50 cm long around the
water
rell and drainage pipe from the water rell and drainage pipe port.
FusionDC1000A Prefabricated All-in-One Data
Center
Installation Guide (IT Scenario) 8 Installing Devices Inside the Pre-fab. Module
Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd. 73