Figure 8-25 Positions of the threaded adapter and high-pressure hose
(1) Threaded adapter (2) High-pressure hose
Step 5 Connect the wiring terminal of the pressure announciator.
NO TICE
Before connecting the cable, verify that the cable is the pressure announciator
cable by checking the cable label.
The cable is polarity insensitive.
Figure 8-26 Position of the cable to the pressure announciator
Step 6 Connect the interconnection terminal of the re alarm control panel to the cable
interconnection terminal with a terminal resistor.
NO TE
Before connecting the cable, verify that the cable is the electromagnetic valve cable by
checking the cable label.
Connect the red wire to the red wire, and connect the black wire to the black wire.