Device Commissioning > Maintenance > Inverter ON/OFF on the app
and send a shutdown command. Set the DC switch to OFF. Go to Step 2
to check other PV strings. Then go to Step 8.
If the Low Insulation Resistance alarm is still reported one minute after
the DC is supplied, go to Step 5.
If not, go to Step 5.
Step 5 Set the DC switch to OFF, disconnect the possible faulty PV modules and
corresponding optimizers from the PV string, and connect a DC extension cable
with an MC4 connector to the adjacent PV modules or optimizers. Set the DC
switch to ON and view the alarm information.
If the Low Insulation Resistance alarm is not reported one minute after the
DC is supplied, the fault occurs on the disconnected PV module and optimizer.
Choose Device Commissioning > Maintenance > Inverter ON/OFF on the
app and send a shutdown command. Go to Step 7.
If the Low Insulation Resistance alarm is still reported one minute after the
DC is supplied, the fault does not occur on the disconnected PV module or
optimizer. Go to Step 6.
Step 6 Set the DC switch to OFF, reconnect the removed PV module and optimizer, and
repeat Step 5 to check the adjacent PV modules and optimizers.
Step 7 Determine the position of the ground insulation fault.
1. Disconnect the possible faulty PV module from the optimizer.
2. Set the DC switch to OFF.
3. Connect the possible faulty optimizer to the PV string.
4. Set the DC switch to ON. If the solar inverter status is Shutdown: Command,
choose Device Commissioning > Maintenance > Inverter ON/OFF on the
app and send a startup command. Check whether the Low Insulation
Resistance alarm is reported.
If the Low Insulation Resistance alarm is not reported one minute after
the solar inverter is powered on, the PV module is faulty. Choose Device
Commissioning > Maintenance > Inverter ON/OFF on the app and send
a shutdown command.
If the Low Insulation Resistance alarm is still reported one minute after
the solar inverter is powered on, the optimizer is faulty.
5. Set the DC switch to OFF. Replace the faulty component to rectify the
insulation resistance fault. Go to Step 2 to check other PV strings. Then go to
Step 8.
Step 8 If the solar inverter connects to batteries, turn on the auxiliary power switch of the
battery and then the battery switch. Set the DC switch to ON. If the solar inverter
status is Shutdown: Command, choose Device Commissioning > Maintenance >
Inverter ON/OFF on the app and send a startup command.
----End
SUN2000-(3KTL-10KTL)-M1
User Manual E Locating Insulation Resistance Faults
Issue 02 (2020-11-20) Copyright © Huawei Technologies Co., Ltd. 116

Table of Contents

Other manuals for Huawei SUN2000-3KTL-M1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei SUN2000-3KTL-M1 and is the answer not in the manual?

Huawei SUN2000-3KTL-M1 Specifications

General IconGeneral
ModelSUN2000-3KTL-M1
TypeString Inverter
Max. DC Input Voltage600 V
MPPT Voltage Range90 V - 560 V
Rated AC Output Power3000 W
Max. AC Output Power3300 W
Nominal AC Voltage220 V / 230 V / 240 V
AC Voltage Range180 V - 280 V
AC Output Frequency50 Hz / 60 Hz
Max. Efficiency98.6%
MPPT Trackers2
DC Inputs per MPPT1
Max. Input Current per MPPT11 A
Operating Temperature Range-25°C to +60°C
Cooling MethodNatural Convection
Protection DegreeIP65
Max. DC Input Power4500 W
CommunicationRS485
Dimensions (W x H x D)365 mm x 365 mm x 156 mm