EasyManuals Logo

Huawei UPS5000-A-H Series User Manual

Huawei UPS5000-A-H Series
175 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #133 background imageLoading...
Page #133 background image
Procedure
Step 1 After conrming that the battery string is properly connected, turn on the battery
string input switch. If there are multiple battery strings, turn on the switch for
each battery string and then the general switch between the battery strings and
the UPS. The No battery alarm on the MDU disappears.
Step 2 Turn on the downstream output switch to supply power to loads.
----End
5.2 Setting the T/H Sensor
Context
The ambient T/H sensor has been installed by referring to the installation section.
The ambient T/H sensor can also be used as a battery temperature sensor. The
monitoring module distinguishes these two types of sensors through their DIP
switch settings.
Procedure
Step 1 Set the DIP switch.
Figure 5-2 DIP switch (02312PBL)
NO TE
DIP switches 1–6 are used to set the device address, DIP switch 7 is reserved, and DIP switch
8 is used to switch the temperature display mode.
Figure 5-3 DIP switch (02310NBS)
UPS5000-A-(30 kVA-120 kVA)
User Manual 5 Single UPS Commissioning
Issue 17 (2024-02-21) Copyright © Huawei Digital Power Technologies Co., Ltd. 124

Table of Contents

Other manuals for Huawei UPS5000-A-H Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei UPS5000-A-H Series and is the answer not in the manual?

Huawei UPS5000-A-H Series Specifications

General IconGeneral
BrandHuawei
ModelUPS5000-A-H Series
CategoryUPS
LanguageEnglish

Related product manuals