Item Standard
Conducted susceptibility
(CS)
EN 61000-4-6
EN/IEC 62040-2
IEC 61000-4-6
Radiated susceptibility
(RS)
EN 61000-4-3
EN/IEC 62040-2
IEC 61000-4-3
Electrical fast transient
(EFT)
EN/IEC 62040-2
IEC 61000-4-4
Surge EN/IEC 62040-2
IEC 61000-4-5
Power magnetic
susceptibility (PMS)
IEC 61000-4-8
Voltage dips and short
interruptions
IEC 61000-4-11
Inrush current 2 kA. Standard products do not have surge protection modules.
3.5 Mains Input Electrical Specications
Item
Specications
Input system Three-phase, four-wire, and PE
Rated input
voltage
380/400/415 V AC (line voltage)
Input voltage 80–280 V AC (phase voltage)
● UPS5000-A-30KTTL/UPS5000-A-40KTTL/UPS5000-A-80KTTL:
0–40°C: not derated at 176–280 V AC; derated to 40% load at 176–80 V
AC
● UPS5000-A-60KTTL-H/UPS5000-A-120KTTL-H:
– 30–40°C: not derated at 198–280 V AC; derated to 35% load at 198–80
V AC
– 0–30°C: not derated at 187–280 V AC; derated to 35% load at 187–80
V AC
● UPS5000-A-60KTTL/UPS5000-A-120KTTL:
– 30–40°C: not derated at 187–280 V AC; derated to 40% load at 187–80
V AC
– 0–30°C: not derated at 176–280 V AC; derated to 40% load at 176–80
V AC
UPS5000-A-(30 kVA-120 kVA)
User Manual 3 Technical Specications
Issue 17 (2024-02-21) Copyright © Huawei Digital Power Technologies Co., Ltd. 55