NO TICE
After you press the EPO button, the UPS supplies no power, and the loads
powers o.
If the UPS is in maintenance bypass mode, the UPS still supplies power after
you press the EPO button.
Procedure
Step 1 Press the EPO buttons connected to the dry contact cards on all UPSs one by one
or press the general EPO button. All UPSs enter the EPO state.
----End
9.6 Clearing the EPO State
Procedure
Step 1 Turn o the EPO switch.
Step 2 Clear the EPO alarm.
LCD
On the main menu screen, choose Alarms > Clear Faults. In the displayed
dialog box, press
to clear the EPO alarm.
WebUI
On the WebUI, choose Monitoring > UPS System > Running Control and
click Clear Fault. The EPO alarm is cleared.
Step 3 View active alarms and ensure that the EPO alarm is cleared. If the input of the
system bypass is normal, the UPS switches to the bypass mode.
LCD
On the main menu screen, choose Alarms > Active Alarms to check that the
EPO alarm has been cleared.
WebUI
On the WebUI, choose Home > Active Alarm to check that the EPO alarm
has been cleared.
Step 4 Start the inverter.
----End
UPS5000-A-(30 kVA-120 kVA)
User Manual 9 FAQ
Issue 17 (2024-02-21) Copyright © Huawei Digital Power Technologies Co., Ltd. 163

Table of Contents

Other manuals for Huawei UPS5000-A-H Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei UPS5000-A-H Series and is the answer not in the manual?

Huawei UPS5000-A-H Series Specifications

General IconGeneral
BrandHuawei
ModelUPS5000-A-H Series
CategoryUPS
LanguageEnglish

Related product manuals