EasyManuals Logo

Huawei UPS5000-A-H Series User Manual

Huawei UPS5000-A-H Series
175 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #135 background imageLoading...
Page #135 background image
Step 2 Set UI parameters.
NO TICE
The address set on the software must be the same as the address set on the DIP
switch. Otherwise, the communication fails.
The DIP switch address of an ambient T/H sensor ranges from 32 to 44.
LCD: Choose System Info > Settings > Comm. Settings > Amb. T/H Sensor,
and set Start address and Quantity.
WebUI: Choose System Settings > Comm. Settings > Amb. T/H Sensor, and
set Start address and Quantity.
When an ambient T/H sensor is used as a battery temperature sensor, the DIP
switch address ranges from 16 to 28.
LCD: Choose System Info > Settings > Comm. Settings > Batt Temp Sensor,
and set Start address and Quantity.
WebUI: Choose System Settings > Comm. Settings > Batt Temp Sensor, and
set Start address and Quantity.
----End
5.3 Setting BCB Parameters
Prerequisites
A BCB box is installed.
Procedure
Step 1 Choose Settings > Dry Contact Set on the main menu screen, set MUE05A
connection to Enable, and set BCB connection [OL] and Battery breaker [STA]
to Enable.
Figure 5-4 BCB connection settings
----End
5.4 Setting ECO Mode
Context
The UPS is set to non-ECO mode by default. Set the UPS to ECO mode as
required.
UPS5000-A-(30 kVA-120 kVA)
User Manual 5 Single UPS Commissioning
Issue 17 (2024-02-21) Copyright © Huawei Digital Power Technologies Co., Ltd. 126

Table of Contents

Other manuals for Huawei UPS5000-A-H Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei UPS5000-A-H Series and is the answer not in the manual?

Huawei UPS5000-A-H Series Specifications

General IconGeneral
BrandHuawei
ModelUPS5000-A-H Series
CategoryUPS
LanguageEnglish

Related product manuals