FC6A S
ERIES
M
ICRO
S
MART
A
LL
-
IN
-O
NE
T
YPE
U
SER
’
S
M
ANUAL
FC9Y-B1722 2-93
2: P
RODUCT
S
PECIFICATIONS
Wiring Arrangement and Wiring Examples
• Do not connect a thermocouple to a part with hazardous voltage (60V DC or peak 42.4V DC or higher part).
• Before turning on the power, please check that the wiring is correct. If the wiring is incorrect, the analog cartridge may
be damaged. When the analog cartridge may malfunction due to noise, wire it with a shielded cable and connect both
ends to the FG.
• When connecting cables to the analog cartridges, the tightening torque is 0.22 to 0.25 Nm.
Caution
FC6A-PK2AV FC6A-PK2AW
FC6A-PJ2A FC6A-PJ2CP
Analog Voltage Input Device
0 to 10 V
+–
OUT1
+–NC
Analog Voltage Input Device
0 to 10 V
+–
OUT0
+–NC
Analog Voltage Input Device
4 to 20 mA
–+
OUT0
NC – +
Analog Voltage Input Device
4 to 20 mA
+–
OUT1
NC +–
Analog Current Output Device
0 to 20 mA
4 to 20 mA
–+
IN1
+–+
Analog Current Output Device
0 to 10 V
+–
IN0
+–+
Thermocouple
Resistance Thermometer
Pt / Ni
A
BB’
IN0
ABB’
+–NC
+
–
IN1
ABB’
+–NC