EasyManuals Logo

iDect FC6A series User Manual

iDect FC6A series
474 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #395 background imageLoading...
Page #395 background image
FC6A S
ERIES
M
ICRO
S
MART
A
LL
-
IN
-O
NE
T
YPE
U
SER
’
S
M
ANUAL
FC9Y-B1722 11-27
11: SD M
EMORY
C
ARD
Creating the autoexec.ini File
The autoexec.ini file is created according to the file format described in this section. By using WindLDR, the autoexec.ini file can be
created by configuring a dialog box and without needing to be aware of the file format.
Note: To create the autoexec.ini file using Notepad or another text editor, type in the sections, keys, and parameters according to the file format
and save the file as "autoexec.ini".
Autoexec File Format
The autoexec file is made up of the following three sections.
The keys and parameters are described for each section.
If there is no key or if the specified parameter is not applicable, the default value is used for operation.
â–  [COMMON_SETTING] section keys and parameters
â–  [PROGRAM_DOWNLOAD] section keys and parameters
Section Description
[COMMON_SETTING] The section that describes the autoexec.ini file action.
[PROGRAM_DOWNLOAD] The section that describes the operation when downloading data from the SD memory card.
[PROGRAM_UPLOAD] The section that describes the operation when uploading data to the SD memory card.
Key Description Parameter Default Value
loading_direction Specifies the autoexec file action.
none No download or upload is performed.
none
download
A download is performed from the SD
memory card according to the
[PROGRAM_DOWNLOAD] section.
upload
An upload is performed to the SD memory
card according to the [PROGRAM_UPLOAD]
section.
Key Description Parameter Default Value
src_file
Specifies the file name of the ZLD file
that will be downloaded from the SD
memory card.
Specify the name of a ZLD file in the FCDATA01 PROGRAM \\
folder.
• The file name is enclosed in quotation marks (" ").
• The file name is a maximum of 128 characters.
However, when downloading the CPU module system
software, output is turned off regardless of this option's
setting.
"download.zld"
auto_start
Specifies the operation status after the
download is executed.
true Set to run after the download is executed.
false
false Set to stop after the download is executed.
clear_data
Specifies whether or not to clear all
device data including keep data after
the user program download is
executed.
The data that will be cleared is inputs,
outputs, internal relays, shift registers,
data registers, timer current values,
and counter current values.
Timer present values, counter preset
values, special internal relays, and
special data registers will not be
cleared.
true
Clears all device data including keep data
after the download is executed.
false
false
Does not clear all device data including keep
data after the download is executed.
clear_error
Specifies whether or not to clear error
information after the download is
executed.
true
Clears error information after the download is
executed.
false
false
Does not clear error information after the
download is executed.

Table of Contents