Intergas Heating Ltd
47
9.2.7 No hot water (DHW)
Flow sensor not functioning.
No voltage at the flow sensor (5V DC).
wiring according to the diagram.
Burner not firing on DHW: S3 faulty.
See burner does not ignite.
9.2.8 Hot water does not reach temperature
Temperature setting for water circuit too
low.
Set the hot water circuit, depending on the desired temperature.
No heat transfer as a result of lime scale or
fouling in the heat exchanger DHW side.
Descale or flush the exchanger DHW side.
Cold water temperature <10°C.
9.2.9 LED on CH pump is flashing alternately red and green.
Mains voltage to high or to low.
Temperature of the pump is to high
Check the water and environment temperature.
9.2.10 LED on CH pump is flashing red.
Reset the pump by shutting of the boiler (stand
by or powerless) for at least
20 seconds.
Note: If the pump is set on “continuously active” (parameter 2 = 1) the boiler
must be made powerless for at least 20 seconds.