Initial start up and operation 
 
Version 3.0 (08/2018) 
36  Translation of original instruction manual 
Error - Settings 
Network Error 
Monitoring the communication between MultiControl and PLC: 
Ignore:  Error is not displayed. 
Warning:  Error is indicated by the fault LED flashing twice. 
  The conveying process is not interrupted. 
Immediate Stop:  Error is indicated by the fault LED flashing twice. 
  The conveying process is interrupted. 
 
If the MultiControl is operated without PLC, we recommend the setting "Ignore". 
If the MultiControl is operated with PLC, we recommend the setting "Immediate 
Stop". 
 
Over Voltage Error 
Too high supply voltage: 
Ignore:  Error is not displayed. 
Warning:  Error is indicated by fault LED flashing six times. 
  The conveying process is not interrupted. 
Immediate Stop:  Error is indicated by fault LED flashing six times. 
  The conveying process is interrupted.