Goodrive200 inverters Function codes
109
Functio
n code
Name
Detailed instruction of parameters
Default
value
Modify
After the users select the corresponding
ACC/DEC
time, the combining 16 binary
bit will change into
decimal bit, and then set the corresponding function
codes.
Setting range: -0x0000~0xFFFF
P10.36
PLC
restart
0:Restart from the first step; stop during
running
(
cause by the stop command, fault or power loss),
run from the first step after restart.
1: Continue to run from the stop frequency
; stop
duri
ng running(cause by stop command and fault),
the inverter will record the running time
automatically, enter into the step
after restart and
keep the remaining running at the setting frequency.
0
P10.37
Multi-step
time unit
0: Seconds; the running time of all step
s is counted
by second
1: Minutes; the running time of all step
s is counted
by minute
0
P11 Group Protective parameters
P11.00
Phase loss
protection
0x00~0x11
LED ones:
0: Input phase loss protection disable
1: Input phase loss protection enable
LED tens:
0: Input phase loss protection disable
1: Input phase loss protection enable
11
P11.01
Sudden
power loss
frequency-de
creasing
0: Enable
1: Disable
0
P11.02
Frequency
decreasing
Setting range: 0.00Hz/s~P00.03
(the Max.
frequency)
10.00Hz/
s