A.1 What this chapter contains   
This chapter contains the technical specifications of the  inverter,  as well  as  provisions  for 
fulfilling the requirements for CE and other marks. 
A.2 Ratings 
A.2.1 Capacity   
Inverter  sizing  is based on  the rated motor current  and power. To  achieve  the rated  motor 
power reference in the table, the rated current of the inverter must be higher than or equal to 
the rated motor current. Also the rated power of the inverter must be higher than or equal to 
the  rated  motor  power.  The  power  ratings  are  the  same  regardless  of  the  supply  voltage 
within one voltage range. 
Note: 
1. The maximum allowed motor shaft power is limited to 1.5 · PN. If the limit is exceeded, 
motor torque and current are automatically restricted. The function protects the input bridge 
of the drive against overload. 
2. The ratings apply at ambient temperature of 40 °C 
3.  It  is  important  to  check  that  in  Common  DC  systems  the  power  flowing  through  the 
common DC connection does not exceed PN. 
A.2.2 Derating 
The load capacity decreases if the installation site ambient temperature exceeds 40 °C, the 
altitude exceeds 1000 metersor the switching frequency is changed from 4 kHz to 8, 12 or 
15 kHz. 
A.2.2.1 Temperature derating 
In the temperature range +40 °C…+50 °C, the rated  output current is decreased by 3% for 
every additional 1 °C. Refer to the below list for the actual derating.