Goodrive200 inverters Basic operation instruction
148
Function
code
Name Detailed instruction of parameters
Default
value
input function
selection
setting source
1:Cunter input, high-speed pulse counter
input terminals
2:Length counting input, length counter
input terminals
P05.50
Lower limit frequency of
HDI
0.00 kHz ~ P05.43 0.00kHz
P05.51
Corresponding setting of
HDI
low frequency setting
-100.0%~100.0% 0.0%
P05.52
Upper limit frequency of
HDI
P05.41 ~50.00kHz 50.00kHz
P05.53
Corresponding setting of
upper limit frequency of
HDI
-100.0%~100.0% 100.0%
P05.54
HDI frequency input filter
time
0.000s~10.000s 0.100s
7.8 Analog output
Goodrive200 series inverters have 2 analog output terminals (0~10V or 0~20mA) and 1 high speed
pulse output terminal. Analog output signals can be filtered separately and the maximum and
minimum values can be adjusted. The analog output signals can be proportional to motor speed,
output frequency, output current, motor torque, motor power, etc.