Goodrive200 inverters                                                                                  Basic operation instruction     
132 
Function 
code 
Name   
Detailed instruction of parameters  Default 
value 
P04.28  Keypad setting voltage 
0.0%~100.0%(the  rated  voltage  of 
motor) 
100.0%
P04.29  Voltage increasing time 
0.0~3600.0s  5.0s 
P04.30  Voltage decreasing time
0.0~3600.0s  5.0s 
P04.31  Maximum output voltage 
P04.32~100.0%(the  rated  voltage  of 
motor) 
100.0%
P04.32  Minimum output voltage 
0.0%~P04.31(the rated voltage of motor)
0.0% 
7.4 Parameters of the motor   
 Physical  accident  may  occur  if  the  motor  starts  up  suddenly  during 
autotune.  Please  check  the  safety  of  surrounding  environment  of  the 
motor and the load before autotune.   
 The  power  is  still  applied  even  the  motor  stops  running  during  static 
autotune.  Please  do  not  touch  the  motor  until  the  autotune  is 
completed, otherwise there would be electric shock.   
 Do not carry out the rotation autotune if the motor is coupled with the 
load,  please  do  not  operate  on  the  rotation  autotune.  Otherwise 
misaction  or  damage  may  occur  to  the  inverter  or  the  mechanical 
devices.  When carry  out  autotune  on the motor which  is  coupled with 
load,  the  motor  parameter  won’t  be  counted  correctly  and  misaction 
may  occur.  It  is  proper  to  de-couple  the  motor  from  the  load  during 
autotune when necessary.   
Goodrive200 series inverters can drive both asynchronous motors and synchronous motors. And 
at  the  same time, they can  support  two  sets  of motor parameters which can  shift between two 
motors through multi-function digital input terminal or communication.