Goodrive200 inverters Basic operation instruction
131
Function
code
Name
Detailed instruction of parameters Default
value
Frequency point 1
P04.04
Motor 1 V/F Voltage
point 1
0.0%~110.0% 00.0%
P04.05
Motor 1 V/F Frequency
point 2
P04.03~ P04.07 00.00Hz
P04.06
Motor 1V/F Voltage point
2
0.0%~110.0% 00.0%
P04.07
Motor 1V/F Frequency
point 3
P04.05~ P02.02 00.00Hz
P04.08
Motor 1V/F Voltage point
3
0.0%~110.0% 00.0%
P04.09
Motor 1 V/F slip
compensation gain
0.0~200.0% 0.0%
P04.10
Motor 1 low frequency
vibration control factor
0~100 10
P04.11
Motor 1 high frequency
vibration control factor
0~100 10
P04.12
Motor 1 vibration control
threshold
0.00Hz~P00.03 (the Max. frequency) 30.00 Hz
P04.26
Energy-saving operation
selection
0: no action
1: automatic energy-saving running
0
P04.27 Voltage Setting Channel
0:Keypad setting voltage: the output
voltage is determined by P04.28;
1:AI1setting voltage;
2:AI2 setting voltage;
3:AI3 setting voltage
4:HDI1 setting voltage
5:Multi-stes setting voltage
6:PID setting voltage
7:MODBUS communication setting
voltage
8~10: Reversed
0