Stop/ 
Reset key 
This  key  is  used  to  stop  in  running 
state  and it  is limited by function  code 
P07.04 
This  key  is  used  to  reset  all  control 
modes in the fault alarm state   
Quick key   
The function of this key is confirmed by 
function code P07.02. 
 
5.3 Keypad displaying   
The keypad displaying state  of Goodrive200 series inverters is  divided into stopping  state 
parameter,  running  state parameter, function code parameter  editing  state  and  fault  alarm 
state and so on.   
5.3.1 Displayed state of stopping parameter   
When the inverter is in the stopping state, the keypad will display stopping parameters which 
is shown in figure 5-2. 
In the stopping state, various kinds of parameters can be displayed. Select the parameters 
to be displayed or not by P07.07. See the instructions of P07.07 for the detailed definition of 
each bit.   
In the stopping state, there are 14 stopping parameters can be selected  to be displayed or 
not. They are: set frequency, bus voltage, input terminals state, output terminals state, PID 
reference, PID feedback, torque  set value, AI1, AI2, AI3, HDI, PLC and the current step of 
multi-step speeds, pulse counting value, length value. P07.07 can select the parameter to be 
displayed  or  not  by  bit  and 》 /SHIFT  can  shift  the  parameters  form  left  to  right, 
QUICK/JOG(P07.02=2) can shift the parameters form right to left.   
5.3.2 Displayed state of running parameters 
After the inverter receives valid  running commands, the  inverter  will  enter into the  running 
state and the keypad will display the running parameters. RUN/TUNE LED on the keypad is